Tel/fax.: +7 (7112) 51-36-88, 50-79-09, +7 771 014 92 92
E-mail: info@agrs.kz
Application:
PGB-50-1-1.2-OG-U1-SG gas regulating unit is designed to reduce high and medium natural gas pressure to a low one and automatic maintenance of this pressure within the specified limits, automatic gas supply shut-off during an emergency increasing or decreasing of outlet pressure beyond allowable values. The unit is applied in gas distribution and gas consumption systems.
Name of the unit:
PGB-50-1-1.2-OG-U1-SG gas regulating unit is equipped with RDBK-50-35 pressure regulator, SG-EKvz-Р-0.75-250/1.6 (1:100) gas flow measuring skid and a gas heating. As well this unit has a main (working) and a backup (bypass) pipelines, with maximum working pressure of 1.2 MPa, a climatic version for moderate climate (N1).
Basic technical data and description:
The unit is designed for operation outdoors in macroclimatic areas with moderate climate (N) and the 1st location category.
Designed snow load 180 kgf/m2 conforms the requirements of the 3rd territorial area; wind load 48 kgf/m2 as well conforms the requirements of the 4th territorial area.
In the compartment with processing equipment explosion hazard area class is V-1a and complies with the requirements of the Russian Electrical Code (PUE).
Fire hazard category of the unit complies with the Russian fire safety regulations NPB 105-03.
– in technological compartment – А;
– in a heating compartment – G;
– in compartment with processing equipment – D.
Basic technical parameters and description of the unit are to comply with the data in the below shown Table.
Name of parameter |
Value |
1 |
2 |
1 Maximum inlet pressure, MPa |
1,2 |
2 Setting range of regulator outlet pressure, MPa |
0,001…0,06 |
3 Throughout capacity under inlet pressure 0.1 MPa, m3/h, not less |
900 |
4 Setting range for the spring-loaded dump valve actuation |
1,0…5,0 |
5 Setting range for the safety shut-off valve actuation, kPa during decreasing of outlet pressure Рout. during increasing of outlet pressure Рout. |
0,0003…0,003 0,003…0,075 |
6 Gas flow measuring skid |
SG-EKvz-Р-0.75-250/1.6 |
7 Gas meter |
RVG G25 |
8 Gas volume corrector |
ЕК-260 |
9 Measuring range Qmin /Qmax |
1:100 |
10 Qmin under excessive pressure Pex. = 0.0012 MPa, m3/h |
2,5 |
11 Qmax under excessive pressure Pex. = 0.0012 MPa, m3/h |
250 |
12 Working pressure range, MPa |
0,15…0,75 |
13 Gas temperature range, °С |
-20…+60 |
14 Limits of allowable relative error of volume measuring, %: - flow range from 0.1 Qmax to Qmax - flow range from Qmin to 0.1 Qmax |
±1,5 ±2,5 |
15 Allowable pressure differential in the measuring system at maximum capacity Qmax, kPa, not more |
2,6 |
16 Maximum filter differential, kPa, not more |
10 |
17 Gas pressure in the heater, kPa |
2 |
18 Nominal heat power of the heater, kW |
12,2 |
19 Capacity of the heater, m3/h |
1,42 |
20 Voltage, V |
220 |
21 Overall dimensions, not more (LxWxH), m |
6,25х2,5х2,8 |
22 Weight, not more, kg |
4500 |