Automated Gas Distribution Modular Station is designed to reduce a high pressure of a natural and associated petroleum gas to the specified low pressure and its maintenance with a required accuracy as well as to measure gas flow and odorize gas before its supplying to consumers.
Name, parameters and specifications |
Value |
|
1 |
2 |
|
Minimum gas pressure at the inlet, MPa |
2,6 |
|
Maximum gas pressure at the inlet, MPa |
5,5 |
|
Testing gas pressure, MPa |
8,25 |
|
Maximum gas flowrate, Nm3/h |
to a boiler house |
2600 |
mobile automatic power plant |
6600 |
|
Minimum gas flowrate, Nm3/h, |
to a boiler house |
300 |
mobile automatic power plant |
500 |
|
Gas pressure, MPa |
to a boiler house |
0,6 |
mobile automatic power plant |
1,2 |
|
Gas temperature at the inlet, 0С |
max |
+ 28 |
min |
- 55 |
|
Gas temperature at the outlet, 0С |
+ 30 |
|
Accuracy of gas pressure maintenance at the AGDS outlet, % |
±5 |
|
Design service life before overhaul, not less than, h |
175200 |
|
Main power supply, V |
380/220 |
|
Emergency voltage supply, V |
220 |
|
Number of outlets to consumers |
two |
|
Allowable seismicity of the area for station installation, magnitude on the Richter scale |
6 |
|
Dimensions (length×width×height), m: - process control unit - gas heating unit |
11,6×3,36×3,0 12,0×3,5×3,15 |
|
Weight, not more than, kg: - process control unit - gas heating unit |
18000 22000 |