Tel/fax.: +7 (7112) 51-36-88, 50-79-09, +7 771 014 92 92
E-mail: info@agrs.kz
Name | Value | |
AGDS flowrate | nominal | 60.000 Nm³/h |
operating | 55.000 Nm³/h | |
Inlet gas pressure (Рin.) | 2.0-5.5 MPa (to 10.0 MPa) | |
Number of outlets | 2 | |
Outlet gas pressure (Рout) | 1 outlet | 0,6 MPa |
2 outlets | 1,2 MPa | |
AGDS flowrate for every outlet | 1 outlet | 300…30.000 Nm³/h |
2 outlets | 200…25.000 Nm³/h | |
Diameter of the inlet pipeline | DN200 | |
Diameter of the outlet pipeline | 1 outlet | DN300 |
2 outlets | DN200 | |
Backup of the reduction system flowrate | 100% backup | |
Accuracy of gas pressure maintenance at the AGDS outlet | ± 5% | |
Odorization | automatic | |
Emergency alarm | automatic: control and security and fire alarm | |
Electric power. Power consumption, kW | 4.0 (220V) | |
Weight, not more than | 63t |