Application
PGB-13V-2-0.6-OG-U1-SG gas regulating units are designed for gas purification from mechanical impurities, commercial gas flow measuring, pressure reducing from high to medium and automatic maintenance of the pressure within the specified limits, automatic gas supply shut-off during an emergency increasing or decreasing of outlet pressure beyond allowable values, automatic collection, recording and remote transmission of information about the unit operation. The unit is applied in gas distribution and gas consumption systems.
Specification:
1.2.1 The unit is designed for operation outdoors in macroclimatic areas with moderate climate (N) and the 1st location category.
1.2.2 Designed snow load 120 kgf/m2 conforms the requirements of the 2nd territorial area; wind load 38 kgf/m2 as well conforms the requirements of the 2nd territorial area.
1.2.3 Basic parameters and description are shown in the below Table 1.
Table 1
Name of parameter | Value |
1 | 2 |
Setting range of regulator outlet pressure: outlet 1 (Рout1), MPa outlet 2 (Рout2), MPa |
0,06…0,6 0,06…0,6 |
Setting range for the spring-loaded dump valve actuation, MPa | 0,3…0,7 |
Setting range for the safety shut-off valve actuation: during decreasing of outlet pressure, MPa during increasing of outlet pressure, MPa |
0,15…0,5 Рвых (но не менее 0,0009 Мпа) 1,25…1,5 Рвых |
Measuring system | KI-STG-B-80/400-10А-I-M |
Gas meter | STG-80-400 |
Gas volume corrector | BK-10АІ |
1 | 2 |
Measuring range (Qmin /Qmax) | 1:30 |
Qmin, m3/h under normal conditions | 13 |
Qmax, m3/h under normal conditions | 400 |
Absolute pressure range, MPa | from 0.1 to 1.0 |
Gas temperature range, °С | from -20 to +50 |
Limits of allowable relative error of volume measuring, %: - flow range диапазон расходов from 0.2 Qmax to Qmax - flow range from Qmin to 0.2 Qmax |
±1,5±2,5 |
Maximum capacity of the reduction line under inlet pressure Рin=0.4 MPa: outlet 1, m3/h outlet 2, m3/h |
1750 1750 |
Maximum capacity of the gas flow measuring unit under inlet pressure Рin=0.3 MPa (Рin=Рout – unit operation without reduction): outlet 1, m3/h outlet 2, m3/h |
1600 1600 |
Maximum pressure differential in measuring system, kPa | 2,3 |
Filtration degree of the particles with linear dimensions that is more than 10 µm, %, not less | 98 |
Maximum filter differential, kPa, not more | 10 |
Overall dimensions, not more (LхWхH), m | 6,05х3,12х3,06 |
Weight, not more, kg | 7000 |